Everything about Ventilation Architecture totally explained
Ventilation is the intentional movement of
air from outside a building to the inside. It is the
V in
HVAC. With clothes dryers, and combustion equipment such as
water heaters,
boilers, fireplaces, and woodstoves, their exhausts are often called
vents or
flues — this shouldn't be confused with
ventilation. The vents or flues carry the products of combustion which have to be expelled from the building in a way which doesn't cause harm to the occupants of the building. Movement of air between indoor spaces, and not the outside, is called
transfer air.
Ventilation air, as defined in
ASHRAE Standard 62.1 and the
ASHRAE Handbook, is that air used for providing acceptable
indoor air quality. When people or animals are present in buildings, ventilation air is necessary to dilute odours and limit the concentration of
carbon dioxide and airborne pollutants such as respirable suspended particles (RSPs) and volatile organic compounds (VOCs). Ventilation air is often delivered to spaces by mechanical systems which may also heat, cool, humidify and dehumidify the space. Air movement into buildings can occur due to uncontrolled
infiltration of outside air through the building fabric (see
stack effect) or the use of deliberate
natural ventilation strategies. Advanced air filtration and treatment processes such as
scrubbing, can provide ventilation air by cleaning and recirculating a proportion of the air inside a building.
In certain applications, such as submarines, pressurized aircraft, and spacecraft, ventilation air is also needed to provide
oxygen, and to dilute carbon dioxide for survival. Buildings normally have sufficient air leakage to prevent dangerous levels of carbon dioxide. Inadequate ventilation in a densely occupied room can cause the level of carbon dioxide to increase leading to sleepiness and reduced efficiency at work. This is a matter of concern in schools where attentiveness and learning ability may be adversely affected.
In commercial, industrial, and institutional (CII) buildings, and modern jet aircraft, return air is often recirculated to the air handler. A portion of the supply air is normally exfiltrated through the building envelope or exhausted from the building (for example, toilet or kitchen exhaust) and is replaced by outside air introduced inot the return air stream. The rate of ventilation air required, most often provided by this mechanically-induced outside air, is often determined from
ASHRAE Standard 62.1 for CII buildings, or
62.2 for low-rise residential buildings, or similar standards.
The
ventilation rate, for CII buildings, is normally expressed by the volumetric flowrate of outside air being introduced to the building. The typical units used are cubic feet per minute (commonly abbreviated as CFM), or, in metric units, liters per second (L/s). The ventilation rate can also be expressed on a per person or per unit floor area basis, such as CFM/p or CFM/ft², or as
air changes per hour.
For residential buildings, which mostly rely on
infiltration for meeting their ventilation needs, the common ventilation rate measure is the number of times the whole interior volume of air is replaced per hour, and is called
air changes per hour (
I or
ACH; units of 1/h). ACHs of 0.5 to 1.5 are common in modern U.S. homes under winter design weather conditions.
If smoking is allowed indoors, ventilation air is needed in sufficient quantities to dilute the airborne contaminants. Banning indoor
tobacco smoking and the use of candles,
air fresheners, incense, and other generators of air contaminants is much more effective for improving
indoor air quality.
Combustion (for example,
fireplace,
gas heater,
candle,
oil lamp, etc.) consumes oxygen and produces replaced by carbon dioxide other unhealthy
gases and
smoke), requiring ventilation air. An open
chimney promotes infiltration (for example natural ventilation) because of the negative pressure change induced by the
buoyant, warmer air leaving through the chimney. The warm air is typically replaced by heavier, cold air.
Ventilation in a structure is also needed for removing
water vapor, produced by
respiration, burning, and
cooking, and for removing odors, for example, from a
toilet or
kitchen. If water vapor is permitted to accumulate, it may damage the structure,
insulation, or finishes. When operating, an
air conditioner usually removes excess moisture from the air. A
dehumidifier may also be appropriate for removing airborne moisture.
Types of ventilation
- Mechanical or forced ventilation: through an air handling unit or direct injection to a space by a fan. A local exhaust fan can enhance infiltration or natural ventilation, thus increasing the ventilation air flow rate.
- Natural ventilation occurs when the air in a space is changed with outdoor air without the use mechanical systems, such as a fan. Most often natural ventilation is assured through operable windows but it can also be achieved through temperature and pressure differences between spaces. Open windows or vents are not a good choice for ventilating a basement or other below ground structure. Allowing outside air into a cooler below ground space will cause problems with humidity and condensation.
- Infiltration is separate from ventilation, but is often used to provide ventilation air
Ventilation equipment
Fume hood
Biological safety cabinet
Dilution ventilation
Room air distribution
Heat recovery ventilation
Natural ventilation
Natural ventilation is the process of supplying and removing air through an indoor space by natural means. There are two types of natural ventilation occurring in buildings: wind driven ventilation and stack ventilation. The pressures generated by buoyancy, also known as 'the stack effect', are quite low while wind pressures are usually far greater.
Demand Controlled Ventilation (DCV)
DCV makes it possible to maintain proper ventilation and improve air quality while saving energy. ASHRAE has determined that: "It is consistent with the Ventilation rate procedure that Demand Control be permitted for use to reduce the total outdoor air supply during periods of less occupancy." That means the unit - using CO2 sensors and a CO2 setpoint selected for the required ventilation rate - will control the amount of ventilation for the actual number of occupants. During design occupancy, a unit with the DCV system will deliver the same amount of outdoor air as a unit using the ventilation-rate procedure. However, DCV can generate substantial energy savings whenever the space is occupied below the design level.
Further Information
Get more info on 'Ventilation Architecture'.
|
External Link Exchanges
Do you know how hard it is to get a link from a large encyclopaedia? Well we're different and will prove it. To get a link from us just add the following HTML to your site on a relevant page:
<a href="http://ventilation__architecture.totallyexplained.com">Ventilation (architecture) Totally Explained</a>
Then simply click through this link from your web page. Our crawlers will verify your link, extract the title of your web page and instantly add a link back to it. If you like you can remove the words Totally Explained and embed the link in article text.
As long as your link remains in place, we'll keep our link to you right here. Please play fair - our crawlers are watching. Your site must be closely related to this one's topic. Any kind of spamming, dubious practises or removing the link will result in your link from us being dropped and, potentially, your whole site being banned. |